Cremer st - Infrastructure/Kitchen Wiring
Jump to navigation
Jump to search
The printable version is no longer supported and may have rendering errors. Please update your browser bookmarks and please use the default browser print function instead.
People: Paddyd, Phil, Russ
We have sockets and 2.5mm cable aplenty.
Phil's already done the ring main and water heater circuit, and a few sockets. Ms7821 09:28, 16 February 2012 (UTC)
Phil's List
16mm = 26m (non armoured)
P-clips for 16mm = 50
4mm or 6mm T+E = 18m total
Clips to suit = 50
No more 2.5mm required :)
Distribution board to be RCD type
Suggest a 6way board, (room for expansion/reuse elsewhere if we move...)
Breakers 3x32A 1x16A 2x blanking covers
Planned
- Distro box: 3x32A breakers, 1x16A breaker (6 way suggested, so 2xblank)
- 1x63A breaker (presumably C 63, make for 3-phase is currently Hager NC316 C16 400V)
- Cables:
Purpose | Power | Gauge | Length |
---|---|---|---|
Distro | 63A | 10mm^2 | >>1m+14m+4m = 20m |
Oven | 5kW (>>22A) | 4mm^2 | >>2m+2m = 5m |
Hob | 6kW/6.6kW (>>29A) | 4mm^2 | >>2m+2m = 5m |
guess 3kW (13A) | 2.5mm^2 | ||
2.5mm^2 |
Upgrade diameters (4-6, 16-25) if not clipped to a masonry or wooden wall. Phil suggests 18m for the 4mm and 26m for the distro feed
- 50xP-clips for 16mm
- 50xP-clips for 4mm
And to finish off the sockets:
5x Double dry lining boxes (25mm deep or more)- 2x single dry lining boxes (any depth)
Suggested suppliers
- TLC-direct (cheap, but whole drum)
- ?
Back-up option
- 2x4mm runs, one for hob, one for oven
- Put boiler on a fused spur or do a separate 2.5/4mm run for that.