Laboratory 24/Alarm cabling: Difference between revisions

From London Hackspace Wiki
(Created page with '= Overview = The original control unit has been removed, but the frame in which is sat is still present and affixed to the wall above the electrical distribution. All cable runs …')
 
Line 26: Line 26:
; Green/white
; Green/white
: Push to secure (the switch on the outside of the front door.  Originally this would have been used to signal that the last occupant had left and the building was properly secure)
: Push to secure (the switch on the outside of the front door.  Originally this would have been used to signal that the last occupant had left and the building was properly secure)
: NO circuit, goes short when button pushed
: NO circuit (at 4k7) , goes short when button pushed


; Other pairs unused
; Other pairs unused

Revision as of 23:15, 30 July 2010

Overview

The original control unit has been removed, but the frame in which is sat is still present and affixed to the wall above the electrical distribution. All cable runs end up, somehow, at this location. The cable runs are all 8 core, though not all cores need be used on a given run.

The section names in this article match the legends written on the cables themselves.

Front Door + PTS

Blue/yellow
Door switches
NC circuit, impedance increases with one or both doors open
Impedance Door state (viewed when inside, facing out)
open circuit Wire cut/tamper
14k1 Both doors open
9k4 Indeterminate; either of
  • L open, R closed
  • L closed, R open
4k7 Both doors closed, i.e. the normal state
0R tamper
Green/white
Push to secure (the switch on the outside of the front door. Originally this would have been used to signal that the last occupant had left and the building was properly secure)
NO circuit (at 4k7) , goes short when button pushed
Other pairs unused