Archive:CALMU3

From London Hackspace Wiki
Revision as of 16:54, 6 November 2010 by 93.97.176.250 (talk)
Jump to navigation Jump to search

Calmu3 (possibly Calmu3+) from Polymeters Response International. "The first microprocessor-based meter", using "FFT, rather than 'brute-force' DSP" [1]

I think I read somewhere that Calmu3 (minus the +) lacks CoP5 approval.

It may need calibration periodically, but that's probably up to the supplier.

Details

  • Serial no: P99A01869
  • Part no: C3DBD0BC0SJ (3 phase direct, class 1 accuracy, lithium backup, ?)

Interfaces

Software with support


Resources

A later model, with overview.

Presumably ex-PRI consultant on Calmu meters


Serial protocol

1200bps ASCII, \r terminated

Equals symbols are shown on some variables, but presumably wouldn't fit for many.

Once a 'N', 's', 'u' or 'x' are matched, all the remainder of the line is ignored. This suggests they might be for switching to a different protocol, or buggy code. 'u' is definitely buggy.

Commands

F Frequency, updated per sample "F=50.138\r"
N Switch protocol? ff
R (Real?) time "R=15:00:40\r"
S Serial number (presumably "=" doesn't fit) "SP99A01869\r"
s ? "s=", dword 0xa605019e, dword 0, "\r"
u (probably unimplemented) "U\r"
x Switch protocol? ff
B[AVWvw] ?

BAA3123B BV182B85 BW918D2F Bv05B6CE Bw01B525

I[123] Current

I1+15.230 I2+0.0000 I3-0.0300

K[123AVW] ?

K1+2.0700 K2+0.0000 K3+0.0100 KA+2.0600 KV-1.3300 KW+1.6300

L[123] Load?

L1+9.0200 L2+0.0100 L3+0.0200

P[123] ?

P1+1.6400 P2-0.0000 P3+0.0000

Q[123A] ?

Q1=0.769- Q2=1.000+ Q3=1.000+ QA=0.787-

U[AVWvw] Units

UA=2631984 UV=0349470 UW=2549220 Uv=0177551 Uw=0000001

V[123] Voltage

V1+236.75 V2+240.72 V3+242.45

i[123] Current?

i1-5.6300 i2-0.0000 i3-0.0100

p[123] ?

p1-1.3400 p2+0.0000 p3-0.0100

u[AVWvw] ?

UA=2631986 UV=0349470 UW=2549221 Uv=0177552 Uw=0000001

?

Showing 1 related entity.