Anonymous

447 Power: Difference between revisions

From London Hackspace Wiki
1,397 bytes added ,  3 April 2013
in progress ...
(updates)
(in progress ...)
Line 33: Line 33:


'''Box L''': Supplies the two socket rings in the new classroom, plus (part of) central area. Also supplies emergency exit lighting at each end of corridor.
'''Box L''': Supplies the two socket rings in the new classroom, plus (part of) central area. Also supplies emergency exit lighting at each end of corridor.
===Distribution details===
All sub-distribution boxes are supplied via 12mm^2 csa per core armoured cable, unless stated.
;Box A:
:[[User:Solexious]]
;Box B:
:[[User:Solexious]]
;Box C:
:Biolab circuits: 12 double sockets on two circuits,  RCD-protected, 4 double sockets on single circuit, no RCD.
:Wet room: presently undefined: two MCB spaces reserved, all RCD-protected. One 6A lighting circuit.
::Total requirement: incomer, 2RCDs, 8 MCBs (6,10,20x2), 2blank - 14 ways total - standard CU products can be used
;Box D:
:[[User:Solexious]]
;Box E:
:Termination only.
;Box F:
:Server: 16A outlet, 1x double socket, no RCD. sep circuits.
:CNC: presently undefined: 4 MCB spaces plus 2 for RCD reserved.
:two circuits for expansion (''room opp boiler entrance?'')
::Total requirement: incomer:2 MCBs (10,16), 8blank - 10 ways total - standard CU products can be used
;Box J:
:'''partially on hold''' pending better definition of area requirements
:Emergency exit lights 6A
::Total requirement: incomer, 5 circuits with RCB - min 8 ways total - standard CU products can be used
;Box K:
:'''on hold''' pending better definition of area requirements. Will require one RCD for inside and one for outside.
::Install 10-way CU as default; MCB choices can be revised subsequently.
;Box L:
:Classroom: 2 rings to extant fittings. RCD-protected
:Emergency Exit lights: 6A
: install 6-way sub-CU