Line 11: | Line 11: | ||
* Distro box: 3x32A breakers, 1x16A breaker | * Distro box: 3x32A breakers, 1x16A breaker | ||
* Cables: | * Cables: | ||
− | {| | + | {| class="wikitable" |
− | ! Purpose !! Power !! Diameter | + | ! Purpose !! Power !! Diameter !! Length |
|- | |- | ||
− | | | + | | Distro || 100A || 16mm || |
|- | |- | ||
− | | | + | | Oven || 5kW (>>22A) || 4mm || |
|- | |- | ||
− | | | + | | Hob || 6kW/6.6kW (>>29A) || 4mm || |
|- | |- | ||
− | | | + | | Water heater || guess 3kW (13A) || 2.5mm || |
|- | |- | ||
− | | Ring main | | 2.5mm | + | | Ring main || || 2.5mm || |
|} | |} | ||
− | Upgrade all | + | Upgrade all diameters (2.5-4, 4-6, 16-25) if not clipped to a masonry or wooden wall. |
=== Suggested suppliers=== | === Suggested suppliers=== |
Revision as of 23:20, 15 February 2012
- Description: wiring for oven anoff M12 full nuts
4 off M12 flat washers (on site) 4 off M10 studding 350mm d hob. Needs to be done by a competent person.
- People: Russ, Paddyd, Phil
We have sockets and 2.5mm cable aplenty.
Planned
- Distro box: 3x32A breakers, 1x16A breaker
- Cables:
Purpose | Power | Diameter | Length |
---|---|---|---|
Distro | 100A | 16mm | |
Oven | 5kW (>>22A) | 4mm | |
Hob | 6kW/6.6kW (>>29A) | 4mm | |
Water heater | guess 3kW (13A) | 2.5mm | |
Ring main | 2.5mm |
Upgrade all diameters (2.5-4, 4-6, 16-25) if not clipped to a masonry or wooden wall.
Suggested suppliers
- TLC-direct (cheap, but whole drum)
- ?
Back-up option
- 2x4mm spurs, one for hob, one for oven
- Leave boiler on electric circuit or do a separate 2.5/4mm run for that.