Cremer st - Infrastructure/Kitchen Wiring: Difference between revisions
From London Hackspace Wiki
m (→Back-up option: but this would) |
No edit summary |
||
Line 10: | Line 10: | ||
! Purpose !! Power !! Diameter !! Length | ! Purpose !! Power !! Diameter !! Length | ||
|- | |- | ||
| Distro || 100A || 16mm || | | Distro || 100A || 16mm || >>1m+14m+4m = 20m | ||
|- | |- | ||
| Oven || 5kW (>>22A) || 4mm || | | Oven || 5kW (>>22A) || 4mm || >>2m+2m = 5m | ||
|- | |- | ||
| Hob || 6kW/6.6kW (>>29A) || 4mm || | | Hob || 6kW/6.6kW (>>29A) || 4mm || >>2m+2m = 5m | ||
|- | |- | ||
| Water heater || guess 3kW (13A) || 2.5mm || | | Water heater || guess 3kW (13A) || 2.5mm || >>2m = 3m | ||
|- | |- | ||
| Ring main || || 2.5mm || | | Ring main || || 2.5mm || >>2m+2.5m+2.5m, 2m+2m = 12m | ||
|} | |} | ||
Revision as of 23:42, 15 February 2012
People: Russ, Paddyd, Phil
We have sockets and 2.5mm cable aplenty.
Planned
- Distro box: 3x32A breakers, 1x16A breaker
- Cables:
Purpose | Power | Diameter | Length |
---|---|---|---|
Distro | 100A | 16mm | >>1m+14m+4m = 20m |
Oven | 5kW (>>22A) | 4mm | >>2m+2m = 5m |
Hob | 6kW/6.6kW (>>29A) | 4mm | >>2m+2m = 5m |
Water heater | guess 3kW (13A) | 2.5mm | >>2m = 3m |
Ring main | 2.5mm | >>2m+2.5m+2.5m, 2m+2m = 12m |
Upgrade all diameters (2.5-4, 4-6, 16-25) if not clipped to a masonry or wooden wall.
Suggested suppliers
- TLC-direct (cheap, but whole drum)
- ?
Back-up option
- 2x4mm runs, one for hob, one for oven
- Put boiler on a fused spur or do a separate 2.5/4mm run for that.