Equipment/SPC1601: Difference between revisions

From London Hackspace Wiki
No edit summary
Line 54: Line 54:
Default behaviour is to act as a fairly dumb power strip - after a few seconds, all the outputs are turned on in sequence and remain on.
Default behaviour is to act as a fairly dumb power strip - after a few seconds, all the outputs are turned on in sequence and remain on.


The control connection is RS232 to the RJ45 'IN' connector, as described in table A.19 of the manual above. This indicates the following connections to a 9-pin PC-AT RS232 connector, assuming the signals are crossed in the same way as a chained PM20i.
The control connection is RS232 to the RJ45 'IN' connector, as described in table A.19 of the manual above. Pinouts on page 45 of ftp://ftp.avocent.com/public/product-upgrades/SPC/SPC%20Hardware%20Manual.pdf
 
{|border="1" cellpadding="5" cellspacing="0"
 
|-
! Name !! RJ45 pin !! direction !! D9 pin !! Name
|-
| CTS  || 1    || <--  || 7  || RTS
|-
| DCD  || 2    || <--  || 4  || DTR
|-
| RXD  || 3    || <--  || 3  || TXD
|-
| GND  || 4    || --    || 5  || GND
|-
| RTS  || 5    || -->  || 8  || CTS
|-
| TXD  || 6    || -->  || 2  || RXD
|-
| DTR  || 7    || -->  || 1  || DCD
|-
| DSR  || 8    || --    || 6  || DSR
|-
|}





Revision as of 22:19, 18 February 2015

PDU
Hackspace Unknown.png
Model Avocent SPC1601
Sub-category Networking
Status Good working order
Accessories male to female IEC leads
Training requirement Yes
ACnode No
Origin Network Faires
Location Basement rack
Maintainers the sysadmin team

This is a 16 port 2U(?) smart power strip connected to the IPKVM box in the rack downstairs. We can use it to power of and on kit in the rack and measure total power consumption of the rack.

current port assignments

TODO

  • Get borg on the pdu
  • Get the hp thing on the pdu
  • graph power usage
  • and loads of other stuff...

Other info

We use the pdu with the ipkvm thing, so this info isn't needed, might come in handy at some point tho.

Admin manual

Default behaviour is to act as a fairly dumb power strip - after a few seconds, all the outputs are turned on in sequence and remain on.

The control connection is RS232 to the RJ45 'IN' connector, as described in table A.19 of the manual above. Pinouts on page 45 of ftp://ftp.avocent.com/public/product-upgrades/SPC/SPC%20Hardware%20Manual.pdf


It doesn't make sense to connect the two DSR pins together. This occurs because in chaining the units, pin 8 is connected anyway by the RJ45 cable and is presumably not used.

Connecting this to a PC running Kermit at 9600 baud, I got an immediate login prompt. The unit I tried had the factory default users set - no groups or usernames, user admin has password pm8. I didn't have to set any special line conditions so it's possible a 3-wire data-only connection would do.

If you need to reset the password, see loopback plug wiring (link pins 1-8, 2-7, 3-6)