(mention the temp sensors and lack of current monitoring.) |
(would help if i had on and off the right way round.) |
||
Line 32: | Line 32: | ||
All on hamming. These are for port 1, for port 2 change the 1.1.1 to 1.1.2 | All on hamming. These are for port 1, for port 2 change the 1.1.1 to 1.1.2 | ||
=== to switch a port | === to switch a port on === | ||
cd ~jasper/lobbypdu | cd ~jasper/lobbypdu | ||
snmpset -v 2c -M +. -c private lobbypdu .iso.org.dod.internet.private.enterprises.serverTech.sentry3.systemTables.outletTable.outletEntry.outletControlAction.1.1.1 i 1 | snmpset -v 2c -M +. -c private lobbypdu .iso.org.dod.internet.private.enterprises.serverTech.sentry3.systemTables.outletTable.outletEntry.outletControlAction.1.1.1 i 1 | ||
=== and | === and off === | ||
cd ~jasper/lobbypdu | cd ~jasper/lobbypdu | ||
snmpset -v 2c -M +. -c private lobbypdu .iso.org.dod.internet.private.enterprises.serverTech.sentry3.systemTables.outletTable.outletEntry.outletControlAction.1.1.1 i 2 | snmpset -v 2c -M +. -c private lobbypdu .iso.org.dod.internet.private.enterprises.serverTech.sentry3.systemTables.outletTable.outletEntry.outletControlAction.1.1.1 i 2 |
Revision as of 12:35, 30 March 2014
- lobbypdu.lan.london.hackspace.org.uk
- usernames 'admn' and 'root' should both work
- Outlet 1 is used for 'fun' things that can be switched of at night, currently the BigClock and Tom's sign in the Lobby
- Outlet 2 currently unused, could be used for doorbot maybe?
- n.b. Not on the UPS
- Although it has 2 ports for temperature and humidity sensors we don't have the actual sensors
- It doesn't do current monitoring.
- http://www.servertech.com/products/switched-pdus/switched-pdu-cw-2h-ipm-2
procedures
All on hamming. These are for port 1, for port 2 change the 1.1.1 to 1.1.2
to switch a port on
cd ~jasper/lobbypdu snmpset -v 2c -M +. -c private lobbypdu .iso.org.dod.internet.private.enterprises.serverTech.sentry3.systemTables.outletTable.outletEntry.outletControlAction.1.1.1 i 1
and off
cd ~jasper/lobbypdu snmpset -v 2c -M +. -c private lobbypdu .iso.org.dod.internet.private.enterprises.serverTech.sentry3.systemTables.outletTable.outletEntry.outletControlAction.1.1.1 i 2